Most transmitters send their measurement as an analog signal: 4–20 mA, 0–20 mA or 0–10 V. The PLC’s analog input turns that signal into a raw number, and your program scales the raw number into engineering units such as bar, °C or litres.

The formula

Every analog scaling is the same straight line between two points:
Example: a pressure transmitter with a 0–10 bar range sends 12 mA.
Siemens S7-1200 and S7-1500 analog inputs use 0 to 27648 for the nominal range. In TIA Portal you do the same calculation with NORM_X (raw count to 0.0–1.0) followed by SCALE_X (0.0–1.0 to engineering units). Other PLC brands use other raw ranges, so set Raw count at 100 % to match your module’s manual.

Calculator

Pick the signal type, enter the transmitter range, and move the slider to see the engineering value and the raw count the PLC reads.

Why 4–20 mA starts at 4 mA

A 4–20 mA loop has a live zero: 0 % of the measuring range is 4 mA, not 0 mA. If the current drops close to 0 mA, the PLC knows the wire is broken or the sensor has failed, instead of reading a valid “0 bar”. Many transmitters follow the NAMUR NE 43 recommendation: the normal signal stays between 3.8 and 20.5 mA, and a current of 3.6 mA or less, or 21 mA or more, signals a fault. The calculator shows a warning in those zones.