Error 1: Missing Panel images

Download has failed due to missing panel image

After TIA v16, while we download the project to your Touch panel, you may see this error sometimes:

Download has failed due to missing panel image..

This error may be caused by , sometime you configure the Panel in Firmware V16 and Download it.

How to solve it:

Jump to this link:

https://support.industry.siemens.com/cs/document/109746530/image-downloads-for-hmi-operator-panels?dti=0&lc=en-WW

Download the Image zip files that matched with your devices and project.

Here are the files inside the zip:

I am using V15.1 Upda4,

The image files are store in:

\Siemens\Automation\Portal_V15_1\Data\Hmi\Transfer

Paste and overwrite these files.

(please make a backup first)

Refer Link:

https://support.industry.siemens.com/tf//WW/en/posts/download-has-failed-due-to-missing-panel-image/234209?page=0&pageSize=10

https://support.industry.siemens.com/tf/ww/en/posts/tia-v15-download-has-failed-due-to-missing-panel-image/189682?page=0&pageSize=10

https://support.industry.siemens.com/tf//WW/en/posts/getting-error-when-downloading-the-project-via-tia-portal-v15/203794?page=0&pageSize=10